The charger must be connected to a dedicated electrical circuit with the following protections:


  • residual current device with a tripping current I∆n=30mA, type A or B

  • dedicated MCB (Miniature Circuit Breaker) or fuse with the nominal current one class higher than the maximum set current. For example:

    • Max charging current         Breaker / Fuse 

32A                                    40A

16A                                    20A

10A                                    13A